EasyManua.ls Logo

ABB Relion 670 series - Fallback Access via Maintenance Menu

ABB Relion 670 series
944 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
132kV 120V
3 3
EQUATION1937 V1 EN (Equation 1)
The following setting should be used: VTprim=132 (value in kV) VTsec=120 (value in V)
4.2.4.2 Examples how to connect, configure and set VT inputs for most commonly
used VT connections
Figure
19 defines the marking of voltage transformer terminals commonly used around
the world.
A
(H1)
B
(H2)
b
(X2)
a
(X1)
A
(H1)
N
(H2)
n
(X2)
a
(X1)
b) c)
A
(H1)
N
(H2)
dn
(X2)
da
(X1)
d)
V
Pri
+ +
V
Sec
a)
ANSI11000175_1_en.vsd
ANSI11000175 V1 EN
Figure 19: Commonly used markings of VT terminals
Where:
a) is the symbol and terminal marking used in this document. Terminals marked with a square
indicate the primary and secondary winding terminals with the same (positive) polarity
b) is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-ground
connected VTs
c) is the equivalent symbol and terminal marking used by IEC (ANSI) standard for open delta
connected VTs
d) is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-phase
connected VTs
It shall be noted that depending on national standard and utility practices the rated
secondary voltage of a VT has typically one of the following values:
100 V
110 V
115 V
120 V
230 V
1MRK 506 369-UUS - Section 4
Analog inputs
Line distance protection REL670 2.2 ANSI 85
Application manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals