IEC140000120-2-en.vsd
IEC140000120 V2 EN
Figure 36: Multiple instances of ANALOGREPORT blocks
Figure 37 shows both instances of BINARYREPORT function blocks. The instance
number is visible in the bottom of each function block. For each instance, there are three
separate BINARYREPORT blocks capable of reporting up to 24 Binary signals (8 Binary
signals in each BINARYREPORT block). These binary signals can be for example dis-
connector or breaker position indications or internal/external protection alarm signals.
IEC140000121-2-en.vsd
IEC140000121 V2 EN
Figure 37: Multiple instances of BINARYREPORT blocks
6.2.3 Operation principle
The Phasor Measurement Unit (PMU) features three main functional principles:
Section 6 1MRK 506 369-UUS -
Wide area measurement system
116 Line distance protection REL670 2.2 ANSI
Application manual