Section 19 Metering
19.1 Pulse-counter logic PCFCNT
19.1.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Pulse-counter logic PCFCNT
S00947 V1 EN
-
19.1.2 Application
Pulse-counter logic (PCFCNT) function counts externally generated binary pulses, for
instance pulses coming from an external energy meter, for calculation of energy
consumption values. The pulses are captured by the binary input module (BIM), and read
by the PCFCNT function. The number of pulses in the counter is then reported via the
station bus to the substation automation system or read via the station monitoring system
as a service value. When using IEC 61850–8–1, a scaled service value is available over the
station bus.
The normal use for this function is the counting of energy pulses from external energy
meters. An optional number of inputs from an arbitrary input module in IED can be used
for this purpose with a frequency of up to 40 Hz. The pulse-counter logic PCFCNT can
also be used as a general purpose counter.
19.1.3 Setting guidelines
Parameters that can be set individually for each pulse counter from PCM600:
Operation: Disabled/Enabled
tReporting: 0-3600s
EventMask: NoEvents/ReportEvents
1MRK 506 369-UUS - Section 19
Metering
Line distance protection REL670 2.2 ANSI 851
Application manual