Name of OUTx Type Description Value when
activated
Value when
deactivated
OUT6 BOOLEAN Output 6 32 0
OUT7 BOOLEAN Output 7 64 0
OUT8 BOOLEAN Output 8 128 0
OUT9 BOOLEAN Output 9 256 0
OUT10 BOOLEAN Output 10 512 0
OUT11 BOOLEAN Output 11 1024 0
OUT12 BOOLEAN Output 12 2048 0
OUT13 BOOLEAN Output 13 4096 0
OUT14 BOOLEAN Output 14 8192 0
OUT15 BOOLEAN Output 15 16384 0
OUT16 BOOLEAN Output 16 32768 0
The sum of the numbers in column “Value when activated” when all OUTx (1≤x≤16) are
active equals 65535. This is the highest integer that can be converted by the ITBGAPC
function block.
17.12 Elapsed time integrator with limit transgression and
overflow supervision TEIGAPC
17.12.1 Identification
Function Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2 device
number
Elapsed time integrator TEIGAPC - -
17.12.2 Application
The function TEIGAPC is used for user-defined logics and it can also be used for different
purposes internally in the IED. An application example is the integration of elapsed time
during the measurement of neutral point voltage or neutral current at earth-fault
conditions.
Settable time limits for warning and alarm are provided. The time limit for overflow
indication is fixed to 999999.9 seconds.
1MRK 506 369-UUS - Section 17
Logic
Line distance protection REL670 2.2 ANSI 809
Application manual