Application
Generic communication function for Single Point Value (SPGAPC) function is used to
send one single logical output to other systems or equipment in the substation. SP16GAPC
can be used to send up to 16 single point values from the application functions running in
the same cycle time. SPGAPC has one visible input and SPGAPC16 has 16 visible inputs
that should be connected in the ACT tool.
Setting guidelines
There are no settings available for the user for SPGAPC.
Generic communication function for Measured Value MVGAPC
Application
Generic communication function for measured values (MVGAPC) function is used to
send the instantaneous value of an analog signal to other systems or equipment in the
substation. It can also be used inside the same IED, to attach a RANGE aspect to an analog
value and to permit measurement supervision on that value.
Setting guidelines
The settings available for Generic communication function for Measured Value
(MVGAPC) function allows the user to choose a deadband and a zero deadband for the
monitored signal. Values within the zero deadband are considered as zero.
The high and low limit settings provides limits for the high-high-, high, normal, low and
low-low ranges of the measured value. The actual range of the measured value is shown
on the range output of MVGAPC function block. When a Measured value expander block
(RANGE_XP) is connected to the range output, the logical outputs of the RANGE_XP are
changed accordingly.
21.2.3.2 Receiving data
The GOOSE data must be received at function blocks. There are different GOOSE
receiving function blocks depending on the type of the received data. Refer to the
Engineering manual for more information about how to configure GOOSE.
Function block type
Data Type
GOOSEBINRCV 16 single point
GOOSEINTLKRCV 2 single points
16 double points
GOOSEDPRCV Double point
GOOSEINTRCV Integer
GOOSEMVRCV Analog value
GOOSESPRCV Single point
GOOSEXLNRCV Switch status
Section 21 1MRK 506 369-UUS -
Station communication
866 Line distance protection REL670 2.2 ANSI
Application manual