18.10.3 Setting guidelines
The settings tAlarm and tWarning are user settable limits defined in hours. The achievable
resolution of the settings is 0.1 hours (6 minutes).
tAlarm and tWarning are independent settings, that is, there is no check if
tAlarm > tWarning.
The limit for the overflow supervision is fixed at 99999.9 hours.
The setting tAddToTime is a user settable time parameter in hours.
Section 18 1MRK 506 369-UUS -
Monitoring
850 Line distance protection REL670 2.2 ANSI
Application manual