ABB Relion 670 series - Example on How to Connect a Wye Connected Three-Phase CT Set to the IED

ABB Relion 670 series
944 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
It shall be noted that depending on national standard and utility practices, the rated
secondary current of a CT has typically one of the following values:
1A
5A
However, in some cases, the following rated secondary currents are used as well:
2A
10A
The IED fully supports all of these rated secondary values.
It is recommended to:
use 1A rated CT input into the IED in order to connect CTs with 1A
and 2A secondary rating
use 5A rated CT input into the IED in order to connect CTs with 5A
and 10A secondary rating
4.2.2.5 Example on how to connect a wye connected three-phase CT set to the
IED
Figure 13 gives an example about the wiring of a wye connected two-phase CT set to the
IED. It gives an overview of the actions which are needed to make this measurement
available to the built-in protection and control functions within the IED as well.
For correct terminal designations, see the connection diagrams valid for
the delivered IED.
Section 4 1MRK 506 369-UUS -
Analog inputs
74 Line distance protection REL670 2.2 ANSI
Application manual