15.7.3 Setting guidelines
The function does not have any parameters available in the local HMI or PCM600.
15.8 Single point generic control 8 signals SPC8GAPC
15.8.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Single point generic control 8 signals SPC8GAPC - -
15.8.2 Application
The Single point generic control 8 signals (SPC8GAPC) function block is a collection of
8 single point commands that can be used for direct commands for example reset of LED's
or putting IED in "ChangeLock" state from remote. In this way, simple commands can be
sent directly to the IED outputs, without confirmation. Confirmation (status) of the result
of the commands is supposed to be achieved by other means, such as binary inputs and
SPGAPC function blocks.
PSTO is the universal operator place selector for all control functions.
Even if PSTO can be configured to allow LOCAL or ALL operator
positions, the only functional position usable with the SPC8GAPC
function block is REMOTE.
15.8.3 Setting guidelines
The parameters for the single point generic control 8 signals (SPC8GAPC) function are
set via the local HMI or PCM600.
Operation: turning the function operation Enabled/Disabled.
There are two settings for every command output (totally 8):
PulseModex: decides if the command signal for output x is Latched (steady) or Pulsed.
tPulsex: if PulseModex is set to Pulsed, then tPulsex will set the length of the pulse (in
seconds).
1MRK 506 369-UUS - Section 15
Control
Line distance protection REL670 2.2 ANSI 741
Application manual