16.2.3.1 Permissive underreache scheme
Set
Operation
=
On
Set
Scheme
type
=
Permissive UR
Set
tCoord
= 0 ms
Set
tSendMin
= 0.1 s
16.2.3.2 Permissive overreach scheme
Set
Operation
=
On
Set
Scheme
type
=
Permissive OR
Set
tCoord
= 0 ms
Set
tSendMin
= 0.1 s
16.2.3.3 Blocking scheme
Set
Operation
=
On
Set
Scheme
type
=
Blocking
Set
tCoord
= 25 ms (10 ms + maximal transmission time)
Set
tSendMin
= 0 s
16.2.3.4 Intertrip scheme
Set
Operation
=
On
Set
Scheme
type
=
Intertrip
Set
tCoord
= 50 ms (10 ms + maximal transmission time)
Set
tSendMin
= 0.1 s
1MRK 506 369-UUS - Section 16
Scheme communication
Line distance protection REL670 2.2 ANSI 761