Ensure that the underreaching zones from both line ends will overlap a sufficient amount
(at least 10%) in the middle of the protected circuit.
8.12.2.7 Tapped line application
C
A
B
BC
ANSI05000224-2-en.vsd
ANSI05000224 V2 EN
Figure 181: Example of tapped line with Auto transformer
This application gives rise to similar problem that was highlighted in section "Influence
of fault current infeed from remote line end" , that is increased measured impedance due
to fault current infeed. For example, for faults between the T point and B station the
measured impedance at A and C will be
Section 8 1MRK 506 369-UUS -
Impedance protection
370 Line distance protection REL670 2.2 ANSI