EasyManua.ls Logo

ABB Relion 670 series - Single-, Two- or Three-Pole Tripping

ABB Relion 670 series
944 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Other back-up functions are connected to the input TRINP_3P as described above for
three-pole tripping. A typical connection for a single-pole tripping scheme is shown in
figure 385.
ANSI05000545=5=en=Original.vsd
BLOCK
BLKLKOUT
TRINP_3P
TRINP_A
TRINP_B
TRINP_C
PS_A
PS_B
PS_C
1PTRZ
1PTRGF
P3PTR
SETLKOUT
RSTLKOUT
CND
TRIP
SMPPTRC
TR_A
TR_B
TR_C
TR1P
TR2P
TR3P
CLLKOUT
BFI_3P
BFI_A
BFI_B
BFI_C
FW
REV
Phase segregated trip A, B and C
from example line differential or
distance protection
Phase selection A, B and C from
external phase selection logic
Trip by communication scheme of
distance protection if required to
provide a single pole trip
Trip by communication scheme of
earth fault protection if required to
provide a single pole trip
To activate lockout for any trip
To reset lockout
Protection functions with 3
phase trip, for example time
delayed overcurrent protection
OR
To prepare 3 phase trip
for any trip signal
SMBRREC
PREP3P
TR3P
ANSI05000545 V5 EN
Figure 385: The trip logic function SMPPTRC (94) used for single-pole tripping
application
17.1.2.3 Single-, two- or three-pole tripping
The single-/two-/three-pole tripping mode provides single-pole tripping for single-phase
faults, two-pole tripping for two-phase faults and three-pole tripping for three-phase
faults. The operating mode is always used together with an autoreclosing scheme with
setting ARMode = 1/2/3 ph or ARMode = 1/2 Ph.
The functionality is very similar to the single-phase scheme described above. However, in
addition to the connections for single phase above, SMBRREC (79) must also be informed
Section 17 1MRK 506 369-UUS -
Logic
794 Line distance protection REL670 2.2 ANSI
Application manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals