events are created from any available signal in the IED that is connected to the Event
function (EVENT). The EVENT function block is used for remote communication.
Analog, integer and double indication values are also transferred through the EVENT
function.
18.5.3 Setting guidelines
The input parameters for the Event function (EVENT) can be set individually via the local
HMI (Main Menu/Settings / IED Settings / Monitoring / Event Function) or via the
Parameter Setting Tool (PST).
EventMask
(Ch_1 - 16)
The inputs can be set individually as:
NoEvents
OnSet, at pick-up of the signal
OnReset, at drop-out of the signal
OnChange, at both pick-up and drop-out of the signal
AutoDetect, the EVENT function makes the reporting decision (reporting criteria for
integers have no semantic, prefer to be set by the user)
LONChannelMask
or
SPAChannelMask
Definition of which part of the event function block that shall generate events:
Disabled
Channel 1-8
Channel 9-16
Channel 1-16
MinRepIntVal
(1 - 16)
A time interval between cyclic events can be set individually for each input channel. This
can be set between 0 s to 3600 s in steps of 1 s. It should normally be set to 0, that is, no
cyclic communication.
It is important to set the time interval for cyclic events in an optimized way
to minimize the load on the station bus.
18.6 Disturbance report DRPRDRE