Table 58: General settings parameters for the Measurement function
Setting Short description Selected
value
Comment
Operation Operation Off/On On Function must be
On
PowAmpFact Amplitude factor to scale power
calculations
1.000 Typically no scaling is required
PowAngComp Angle compensation for phase
shift between measured I & V
0.0 Typically no angle compensation is
required. As well here required
direction of P & Q measurement is
towards protected object (as per IED
internal default direction)
Mode
Selection of measured current
and voltage
Arone Generator VTs are connected between
phases (V-connected)
k Low pass filter coefficient for
power measurement, V and I
0.00 Typically no additional filtering is
required
VGenZeroDb Zero point clamping in % of
Vbase
25% Set minimum voltage level to 25%
IGenZeroDb Zero point clamping in % of Ibase 3 Set minimum current level to 3%
VBase (set in
Global base)
Base setting for voltage level in
kV
15,65 Set generator rated phase-to-phase
voltage
IBase (set in
Global base)
Base setting for current level in A 3690 Set generator rated current
18.2 Gas medium supervision SSIMG (63)
18.2.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Insulation gas monitoring function SSIMG - 63
18.2.2 Application
Gas medium supervision (SSIMG ,63) is used for monitoring the circuit breaker
condition. Proper arc extinction by the compressed gas in the circuit breaker is very
important. When the pressure becomes too low compared to the required value, the circuit
breaker operation shall be blocked to minimize the risk of internal failure. Binary
information based on the gas pressure in the circuit breaker is used as an input signal to the
function. The function generates alarms based on the received information.
Section 18 1MRK 506 369-UUS -
Monitoring
828 Line distance protection REL670 2.2 ANSI