230kV Busbar
300/5
4000/5
100 MVA
G
P Q
100 MVA
15.65kV
ANSI09000041-1-en.vsd
15/0.12kV
V
AB ,
V
BC
,
IED
ANSI09000041 V1 EN
Figure 394: Single line diagram for generator application
In order to measure the active and reactive power as indicated in figure 394, it is necessary
to do the following:
1. Set correctly all CT and VT data and phase angle reference channel PhaseAngleRef
(see Section
“Setting of the phase reference channel”) using PCM600 for analog
input channels
2. Connect, in PCM600, measurement function to the generator CT & VT inputs
3. Set the setting parameters for relevant Measurement function as shown in the
following table:
1MRK 506 369-UUS - Section 18
Monitoring
Line distance protection REL670 2.2 ANSI 827