IEC140000118 V2 EN
Figure 34: Multiple instances of PMUREPORT function block
Figure 35 shows both instances of the PHASORREPORT function blocks. The instance
number is visible in the bottom of each function block. For each instance, there are four
separate PHASORREPORT blocks including 32 configurable phasor channels (8 phasor
channels in each PHASORREPORT block). Each phasor channel can be configured as a
3-phase (symmetrical components positive/negative/zero) or single-phase phasor
(A/B/C).
IEC140000119 V2 EN
Figure 35: Multiple instances of PHASORREPORT blocks
Figure 36 shows both instances of ANALOGREPORT function blocks. The instance
number is visible in the bottom of each function block. For each instance, there are three
separate ANALOGREPORT blocks capable of reporting up to 24 Analog signals (8
Analog signals in each ANALOGREPORT block). These can include for example
transfer of active and reactive power or reporting the milliampere input signals to the PDC
clients as defined in IEEE C37.118 data frame format.
1MRK 506 369-UUS - Section 6
Wide area measurement system
Line distance protection REL670 2.2 ANSI 115
Application manual