EasyManua.ls Logo

ABB Relion 670 series - Page 188

ABB Relion 670 series
944 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
drop DV
C
on series capacitor lags the fault current by 90 degrees. Note that line impedance
X
L1
could be divided into two parts: one between the IED point and the capacitor and one
between the capacitor and the fault position. The resulting voltage V
M
in IED point is this
way proportional to sum of voltage drops on partial impedances between the IED point
and the fault position F, as presented by
( )
M F L1 C
V I j X X= × -
EQUATION1995-ANSI V1 EN (Equation 52)
en06000605_ansi.vsd
~
21
XS
X
L1
IF
V
V
M
Source
Fault voltage
Pre -fault voltage
X
C
Source voltage
V
M
With bypassed
capacitor
With inserted
capacitor
F
X
ANSI06000605 V1 EN
Figure 81: Voltage inversion on series compensated line
en06000606_ansi.vsd
I
F
V
S
V
M
=
x
V
L
x
V
S
I
F
x
V
L
V
S
x
V
C
V
M
x
V
S
With bypassed
capacitor
With inserted
capacitor
ANSI06000606 V1 EN
Figure 82: Phasor diagrams of currents and voltages for the bypassed and inserted
series capacitor during voltage inversion
It is obvious that voltage V
M
will lead the fault current I
F
as long as X
L1
> X
C
. This
situation corresponds, from the directionality point of view, to fault conditions on line
Section 8 1MRK 506 369-UUS -
Impedance protection
182 Line distance protection REL670 2.2 ANSI
Application manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals