Figure 105: Measured impedance at voltage inversion
Forward direction:
Where
X
LLoc
equals line reactance up to the series capacitor(in the picture
approximate 33% of XLine)
X1
is set to (XLindex-XC) · p/100.
p is defined according to figure 103
1,2 is safety factor for fast operation of Zone 1
Compensated line with the series
capacitor not into the reach of zone 1. The
setting is thus:
X1
is set to (XLine-XC) · p/100.
Section 8 1MRK 506 369-UUS -
Impedance protection
208 Line distance protection REL670 2.2 ANSI
Application manual