A
B
Z<
Z<
Z<
C
T
IC
IA
IB
-IB
en05000224.vsd
DOCUMENT11524-IMG869 V1 EN
Figure 145: Example of tapped line with Auto transformer
This application gives rise to similar problem that was highlighted in section "Fault infeed
from remote end" that is, increased measured impedance due to fault current infeed. For
example for faults between the T point and B station the measured impedance at A and C
will be
DOCUMENT11524-IMG3509 V3 EN
(Equation 204)
2
2
1
A C
C Trf CT TB
C
I I V
Z Z Z Z
V
I
=
æ ö
+
æ ö
+ + × ×
ç ÷
ç ÷
è ø
è ø
EQUATION1783-ANSI V1 EN (Equation 205)
Where:
ZAT and ZCT is the line impedance from the B respective C station to the T point.
IA and IC is fault current from A respective C station for fault between T and B.
V2/V1 Transformation ratio for transformation of impedance at V1 side of the transformer to the
measuring side V2 (it is assumed that current and voltage distance function is taken
from V2 side of the transformer).
Section 8 1MRK 506 369-UUS -
Impedance protection
292 Line distance protection REL670 2.2 ANSI
Application manual