EasyManua.ls Logo

ABB Relion 670 series - Page 384

ABB Relion 670 series
944 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2
loa d min
Z
V
S
=
EQUATION1718 V1 EN (Equation 328)
Where:
V the minimum phase-to-phase voltage in kV
S the maximum apparent power in MVA.
The load impedance [Ω/phase] is a function of the minimum operation voltage and the
maximum load current:
min
loa d
ma x
Z
V
3 I
=
×
EQUATION1719 V1 EN (Equation 329)
Minimum voltage V
min
and maximum current I
max
are related to the same operating
conditions. Minimum load impedance occurs normally under emergency conditions.
As a safety margin, it is required to avoid load encroachment under three-
phase conditions. To guarantee correct healthy phase IED operation under
combined heavy three-phase load and ground faults both phase-to-phase
and phase-to-ground fault operating characteristics should be considered.
To avoid load encroachment for the phase-to-ground measuring elements, the set resistive
reach of any distance protection zone must be less than 80% of the minimum load
impedance.
loa d
RFP G 0.8 Z£ ×
EQUATION1720 V1 EN
(Equation 330)
This equation is applicable only when the loop characteristic angle for the single phase-
to-ground faults is more than three times as large as the maximum expected load-
impedance angle. For the case when the loop characteristic angle is less than three times
the load-impedance angle, more accurate calculations are necessary according to equation
146.
Section 8 1MRK 506 369-UUS -
Impedance protection
378 Line distance protection REL670 2.2 ANSI
Application manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals