IED
ZB
Line impedance = ZC
ZA = forward source impedance
IEC07000014_2_en.vsd
IEC07000014 V2 EN
Figure 235: Line application of pole slip protection
If the apparent impedance crosses the impedance line ZB – ZA this is the detection
criterion of out of step conditions, see figure 236.
Section 8 1MRK 506 369-UUS -
Impedance protection
458 Line distance protection REL670 2.2 ANSI
Application manual