EasyManua.ls Logo

ABB Relion 670 series - Page 538

ABB Relion 670 series
944 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Where
I
j
is the capacitive ground fault current at a non-resistive phase-to-ground fault
X
c
is the capacitive reactance to ground
In a system with a neutral point resistor (resistance grounded system) the impedance Z
0
can be calculated as:
c n
0
c n
jX 3R
Z
jX 3R
- ×
=
- +
EQUATION1946 V1 EN (Equation 471)
Where
R
n
is the resistance of the neutral point resistor
In many systems there is also a neutral point reactor (Petersen coil) connected to one or
more transformer neutral points. In such a system the impedance Z
0
can be calculated as:
( )
n n c
0 c n n
n c n n c
9R X X
Z jX // 3R // j3X
3X X j3R 3X X
= - =
+ × -
EQUATION1947 V1 EN (Equation 472)
Where
X
n
is the reactance of the Petersen coil. If the Petersen coil is well tuned we have 3X
n
= X
c
In this case
the impedance Z
0
will be: Z
0
= 3R
n
Now consider a system with an grounding via a resistor giving higher ground fault current
than the high impedance grounding. The series impedances in the system can no longer be
neglected. The system with a single phase to ground fault can be described as in Figure
276.
Section 9 1MRK 506 369-UUS -
Current protection
532 Line distance protection REL670 2.2 ANSI
Application manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals