CLOSECMD
Connect to a binary output for circuit breaker closing command.
COUNT1P, COUNT2P, COUNT3P1, COUNT3P2, COUNT3P3,
COUNT3P4 and COUNT3P5
Indicates the number of auto reclosing shots made for respective shot.
COUNTAR
Indicates the total number of auto reclosing shots made.
INHIBOUT
If the INHIBIT input is activated it is reported on the INHIBOUT output.
INPROGR
Indicates that an auto recloser sequence is in progress, from start until circuit breaker close
command.
MODE
When a valid integer is connected to the MODEINT input, the selected ARMode setting
will be invalid and the MODEINT input value will be used instead. The selected mode is
reported as an integer on the MODE output. The six possible modes are described in Table
47 with their corresponding MODEINT integer value.
PERMIT1P
Permit single-pole trip is the inverse of PREP3P. It can be connected to a binary output
relay for connection to external protection or trip relays. In case of a total loss of auxiliary
power, the output relay drops and does not allow single-pole trip.
PREP3P
Prepare three-pole trip is usually connected to the trip block to force a coming trip to be
a three-pole one. If the auto recloser cannot make a single-pole or two-pole auto reclosing,
the tripping should be three-pole.
READY
Indicates that the auto recloser is ready for a new and complete auto reclosing sequence.
It can be connected to the zone extension if a line protection should have extended zone
reach before auto reclosing.
SETON
Indicates that auto recloser is switched on and operative.