Features in the apparatus control function:
• Operation of primary apparatuses
• Select-Execute principle to give high security
• Selection and reservation function to prevent simultaneous operation
• Selection and supervision of operator place
• Command supervision
• Block/deblock of operation
• Block/deblock of updating of position indications
• Substitution of position indications
• Overriding of interlocking functions
• Overriding of synchronism check
• Pole discrepancy supervision
• Operation counter
• Suppression of mid position
The apparatus control function is realized by means of a number of function blocks
designated:
• Switch controller SCSWI
• Circuit breaker SXCBR
• Circuit switch SXSWI
• Bay control QCBAY
• Bay reserve QCRSV
• Reservation input RESIN
• Local remote LOCREM
• Local remote control LOCREMCTRL
The signal flow between the function blocks is shown in Figure 315. To realize the
reservation function, the function blocks Reservation input (RESIN) and Bay reserve
(QCRSV) also are included in the apparatus control function. The application description
for all these functions can be found below. The function SCILO in the Figure below is the
logical node for interlocking.
When the circuit breaker or switch is located in a breaker IED, two more functions are
added:
• GOOSE receive for switching device GOOSEXLNRCV
• Proxy for signals from switching device via GOOSE XLNPROXY
The extension of the signal flow and the usage of the GOOSE communication are shown
in Figure
316.
1MRK 506 369-UUS - Section 15
Control
Line distance protection REL670 2.2 ANSI 681
Application manual