Trip value rec Fault locator
Sequential of
events
Event recorder
Indications
Disturbance
recorder
Disturbance Report
Binary signals
Analog signals
DRPRDRE
FL
ANSI09000336-2-en.vsdx
AxRADR
BxRBDR
ANSI09000336 V2 EN
Figure 396: Disturbance report functions and related function blocks
For Disturbance report function there are a number of settings which also influences the
sub-functions.
Three LED indications placed above the LCD screen makes it possible to get quick status
information about the IED.
Green LED:
Steady light In Service
Flashing light Internal failure
Dark No power supply
Yellow LED:
Steady light Triggered on binary signal N with SetLEDx = Start (or Start and
Trip)
Flashing light The IED is in test mode
Table continues on next page
1MRK 506 369-UUS - Section 18
Monitoring
Line distance protection REL670 2.2 ANSI 839
Application manual