Where:
1) shows how to connect three individual phase currents from a delta connected three-phase CT set
to three CT inputs of the IED.
2) is the TRM where these current inputs are located. It shall be noted that for all these current inputs
the following setting values shall be entered.
CT
prim
=600A
CT
sec
=5A
CTWyePoint
=
ToObject
ConnectionType
=
Ph-Ph
3)
are three connections made in Signal Matrix Tool (SMT), Application configuration tool (ACT),
which connect these three current inputs to first three input channels of the preprocessing function
block 4). Depending on the type of functions which need this current information, more then one
preprocessing block might be connected in parallel to these three CT inputs.
4)
is a Preprocessing block that has the task to digitally filter the connected analog inputs and
calculate:
fundamental frequency phasors for all three input channels
harmonic content for all three input channels
positive, negative and zero sequence quantities by using the fundamental frequency
phasors for the first three input channels (channel one taken as reference for sequence
quantities)
These calculated values are then available for all built-in protection and control functions within the
IED, which are connected to this preprocessing function block. For this application most of the
preprocessing settings can be left to the default values.
If frequency tracking and compensation is required (this feature is typically required only for IEDs
installed in the generating stations) then the setting parameters
DFTReference
shall be set
accordingly.
Another alternative is to have the delta connected CT set as shown in figure 17: