EasyManua.ls Logo

ABB Relion 670 series - Page 926

ABB Relion 670 series
944 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
sn
R
al a lreq CT L
2
pn n
k ma x
I I
S
E E R R
I I
³ = × + +
æ ö
×
ç ÷
è ø
EQUATION1675 V1 EN (Equation 536)
sn
R
al alreq CT L
2
pn n
kzone1
I I
S
E E R R
I I
³ = × + +
æ ö
×
ç ÷
è ø
EQUATION1676 V1 EN (Equation 537)
where:
I
kmax
Maximum primary fundamental frequency current for close-in forward and reverse
faults (A)
I
kzone1
Maximum primary fundamental frequency current for faults at the end of zone 1
reach (A)
I
pr
The rated primary CT current (A)
I
sr
The rated secondary CT current (A)
I
n
The nominal current of the protection IED (A)
R
ct
The secondary resistance of the CT (W)
R
L
The resistance of the secondary wire and additional load (W). In solidly grounded
systems the loop resistance containing the phase and neutral wires should be used
for phase-to-ground faults and the resistance of the phase wire should be used for
three-phase faults.
In isolated or high impedance grounded systems the resistance of the single
secondary wire can always be used.
S
R
The burden of an IED current input channel (VA). S
R
=0.020 VA/channel for I
r
=1 A
and S
R
=0.150 VA/channel for I
r
=5 A
Table continues on next page
Section 25 1MRK 506 369-UUS -
Requirements
920 Line distance protection REL670 2.2 ANSI
Application manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals