Format: Transparent
Maximum channel delay
Loop time <40 ms continuous (2 x 20 ms)
IED with echo synchronization of differential clock (without GPS clock)
Both channels must have the same route with maximum asymmetry of 0,2-0,5 ms,
depending on set sensitivity of the differential protection.
A fixed asymmetry can be compensated (setting of asymmetric delay in built in HMI
or the parameter setting tool PST).
IED with GPS clock
Independent of asymmetry.
Section 25 1MRK 506 369-UUS -
Requirements
926 Line distance protection REL670 2.2 ANSI