VoltageInput = negSeq
I > = 125% IBase
VDepFact1 = (1-117)/I> = 0.064
2. Values of the logical signals and the service values for SCCFPVOC (51 V) are available on the
local HMI under: Main menu/Tests/Function status/Unbalance protection/
CapBankCascadingFail(51V,2(I>/U<))/SCCFPVOC (51V, 2(I>/U<)):x, where x = instance number.
The Base values, CT and VT ratios are as follows:
2.1. VBase considered is 400 kV
2.2. IBase considered is 3000 A and the calculations are done considering CT
ratio as 3000 A/1 A and VT ratio as 400 kV/110 V
2.3. Rated frequency = 50 Hz
3. Set the constant input voltage as, VA = 63.50° V, VB = 63.5240° V, and VC = 63.5120° V in
secondary at rated frequency.
4. Set the constant input current as, IA = 00° A, IB = 0240° A, and IC = 0120° A in secondary at
rated frequency.
5. Following are the steps to check the operation of Step 1.
Step
No.
Step1 operating characteristic verification Expected output
5-a Inject constant voltages of VA = 1.00° V, VB = 1.0120° V,VC
= 1.0240° V and constant currents of IA = 0.100° A, IB =
0.10120° A, IC = 0.10240° A in secondary at rated
frequency.
PU_ST1 and BFI_3P signal should
be TRUE
Repeat Step 3 and Step 4, to reset PU_ST1 and BFI_3P.
5-b Inject constant voltages of VA = 57.730° V, VB = 57.73120°
V, VC = 57.73240° V and constant currents of IA = 1.100° A,
IB = 1.10120° A, IC = 1.10240° A in secondary at rated
frequency.
PU_ST1 and BFI_3P signal should
be TRUE
Repeat Step 3 and Step 4, to reset PU_ST1 and BFI_3P.
5-c Inject constant voltages of VA = 76.210° V, VB = 76.21120°
V, VC = 76.21240° V and constant currents of IA= 1.260° A,
IB = 1.26120° A, IC = 1.26240° A in secondary at rated
frequency.
PU_ST1 and BFI_3P signal should
be TRUE
6. Repeat Step 3, Step 4 and Step 5 for Step 2 operation, by setting Operation2 (Step 2) Enable, new
values of input currents as per slope characteristics and the VDepFact2 based on the I>> value;
check the output PU_ST2 and BFI_3P.
Verification of zero sequence-based operation
GUID-8EAE0867-4161-4BFF-AE89-BE44F374B6A1 v1
1. Set the following parameters:
Operation = Enable
Operation1 = Enable (Step 1)
CurrentInput = 3×ZeroSeq
1MRK 504 165-UUS Rev. J Section 11
Testing functionality by secondary injection
Transformer protection RET670 215
Commissioning manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved