EasyManua.ls Logo

ABB ret650 - IEC 61850 Generic Communication I;O Functions DPGGIO; Identification; Functionality; Function Block

ABB ret650
670 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IPOS1 IPOS2 Name of displayed string Default string value
0 0 PosUndefined P00
1 0 Position1 P01
0 1 Position2 P10
1 1 PosBadState P11
12.6 IEC 61850 generic communication I/O functions
DPGGIO
12.6.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
IEC 61850 generic communication I/O
functions
DPGGIO - -
12.6.2 Functionality
The IEC 61850 generic communication I/O functions DPGGIO function block is used
to send double indications to other systems or equipment in the substation using
IEC61850. It is especially used in the interlocking and reservation station-wide logics.
12.6.3 Function block
DPGGIO
OPEN
CLOSE
VALID
POSITION
IEC09000075_1_en.vsd
IEC09000075 V1 EN
Figure 155: DPGGIO function block
12.6.4 Signals
Table 252: DPGGIO Input signals
Name
Type Default Description
OPEN BOOLEAN 0 Open indication
CLOSE BOOLEAN 0 Close indication
VALID BOOLEAN 0 Valid indication
Table 253: DPGGIO Output signals
Name
Type Description
POSITION INTEGER Double point indication
Section 12 1MRK 504 135-UEN A
Control
358
Technical manual

Table of Contents

Other manuals for ABB ret650