Section 6  Differential protection
6.1  Transformer differential protection
6.1.1  Functionality
The Transformer differential protection, two-winding T2WPDIF and Transformer
differential protection, three-winding T3WPDIF are provided with internal CT ratio
matching and vector group compensation and settable zero sequence current
elimination.
The function can be provided with two or three three-phase sets of current inputs. All
current inputs are provided with percentage bias restraint features, making the IED
suitable for two- or three-winding transformer arrangements.
Two-winding applications
IEC05000048 V1 EN
two-winding power
transformer
Three-winding applications
IEC05000052 V1 EN
three-winding power
transformer with all
three windings
connected
IEC05000049 V1 EN
three-winding power
transformer with
unconnected delta
tertiary winding
Figure 29: CT group arrangement
for differential
protection and other
protections
The setting facilities cover the application of the differential protection to all types of
power transformers and auto-transformers with or without load tap changer as well as
shunt reactors and local feeders within the station. An adaptive stabilizing feature is
included for heavy through-faults.
1MRK 504 135-UEN A Section 6
Differential protection