16.5.3  Settings
Table 451: GOOSEVCTRCONF Non group settings (basic)
Name
Values (Range) Unit Step Default Description
SendOperation Off
On
- - On Send operation
SendInterval 0.1 - 5.0 s 0.1 0.3 Send interval
ReceiveOperation Off
On
- - On Receive operation
ReceiveInterval 0.1 - 10.0 s 0.1 0.8 Receive interval
16.6  GOOSE voltage control receiving block
GOOSEVCTRRCV
16.6.1  Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE voltage control receiving block GOOSEVCTRR
CV
- -
16.6.2  Functionality
GOOSEVCTRRCV component receives the voltage control data from GOOSE
network at the user defined rate.
This component also checks the received data validity, communication validity and
test mode. Communication validity will be checked upon the rate of data reception.
Data validity also depends upon the communication. If communication is invalid then
data validity will also be invalid. IEC 61850 also checks for data validity using
internal parameters which will also be passed to the DATAVALID output.
16.6.3  Function block
IEC10000252-1-en.vsd
GOOSEVCTRRCV
BLOCK VCTR_RCV
DATAVALID
COMMVALID
TEST
IEC10000252 V1 EN
Figure 241: GOOSEVCTRRCV function block