The settings are visible on the local HMI , under Main menu/Diagnostics/IED
status/Product identifiers
They are very helpful in case of support process (such as repair or maintenance).
17.7.3 Settings
The function does not have any parameters available in the local HMI or PCM600.
17.8 Primary system values PRIMVAL
17.8.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Primary system values PRIMVAL - -
17.8.2 Functionality
The rated system frequency and phasor rotation are set under Main menu/
Configuration/ Power system/ Primary values/PRIMVAL in the local HMI and
PCM600 parameter setting tree.
17.8.3 Settings
Table 493: PRIMVAL Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Frequency 50.0 - 60.0 Hz 10.0 50.0 Rated system frequency
PhaseRotation Normal=L1L2L3
Inverse=L3L2L1
- - Normal=L1L2L3 System phase rotation
17.9 Signal matrix for analog inputs SMAI
17.9.1 Functionality
Signal matrix for analog inputs function (SMAI), also known as the preprocessor
function, processes the analog signals connected to it and gives information about all
aspects of the analog signals connected, like the RMS value, phase angle, frequency,
harmonic content, sequence components and so on. This information is then used by
the respective functions in ACT (for example protection, measurement or
monitoring).
Section 17 1MRK 504 135-UEN A
Basic IED functions
580
Technical manual