Name Values (Range) Unit Step Default Description
U1HiHiLim 0 - 2000000 V 1 96000 High High limit (physical value)
U1HiLim 0 - 2000000 V 1 86000 High limit (physical value)
U1LowLim 0 - 2000000 V 1 71000 Low limit (physical value)
U1LowLowLim 0 - 2000000 V 1 66000 Low Low limit (physical value)
U1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
U2ZeroDb 0 - 100000 m% 1 500 Zero point clamping
U2HiHiLim 0 - 2000000 V 1 96000 High High limit (physical value)
U2HiLim 0 - 2000000 V 1 86000 High limit (physical value)
U2LowLim 0 - 2000000 V 1 71000 Low limit (physical value)
U2LowLowLim 0 - 2000000 V 1 66000 Low Low limit (physical value)
14.1.6.5 Monitored data
Table 351: VMSQI Monitored data
Name Type Values (Range) Unit Description
3U0 REAL - kV 3U0 Amplitude
3U0ANGL REAL - deg 3U0 Angle
U1 REAL - kV U1 Amplitude
U1ANGL REAL - deg U1 Angle
U2 REAL - kV U2 Amplitude
U2ANGL REAL - deg U2 Angle
14.1.7 Phase-neutral voltage measurement VNMMXU
14.1.7.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Phase-neutral voltage measurement VNMMXU
U
SYMBOL-UU V1 EN
-
14.1.7.2 Function block
The available function blocks of an IED are depending on the actual hardware (TRM)
and the logic configuration made in PCM600.
1MRK 504 135-UEN A Section 14
Monitoring
425
Technical manual