The input of this GOOSE block must be linked in SMT by means of
a cross to receive the float values.
The implementation for IEC61850 quality data handling is restricted
to a simple level. If quality data validity is GOOD then the
DATAVALID output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW.
16.10 GOOSE function block to receive a single point value
GOOSESPRCV
16.10.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE function block to receive a
single point value
GOOSESPRCV - -
16.10.2 Functionality
GOOSESPRCV is used to receive a single point value using IEC61850 protocol via
GOOSE.
16.10.3 Function block
GOOSESPRCV
BLOCK ^SPOUT
DATAVALID
COMMVALID
TEST
IEC10000248-1-en.vsd
IEC10000248 V1 EN
Figure 245: GOOSESPRCV function block
16.10.4 Signals
Table 463: GOOSESPRCV Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of function
Section 16 1MRK 504 135-UEN A
Station communication
548
Technical manual