EasyManua.ls Logo

ABB ret650 - Settings; Setting Parameters for Binary Input Modules

ABB ret650
670 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Each binary input has an oscillation count parameter OscillationCountx and an
oscillation time parameter OscillationTimex, where x is the number of the binary input
of the module in question.
4.1.3 Settings
4.1.3.1 Setting parameters for binary input modules
Table 8: BIO_9BI Non group settings (basic)
Name Values (Range) Unit Step Default Description
BatteryVoltage 24 - 250 V 1 110 Station battery voltage
Table 9: BIO_9BI Non group settings (advanced)
Name Values (Range) Unit Step Default Description
Threshold1 6 - 900 %UB 1 65 Threshold in percentage of station battery
voltage for input 1
DebounceTime1 0.000 - 0.100 s 0.001 0.005 Debounce time for input 1
OscillationCount1 0 - 255 - 1 0 Oscillation count for input 1
OscillationTime1 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 1
Threshold2 6 - 900 %UB 1 65 Threshold in percentage of station battery
voltage for input 2
DebounceTime2 0.000 - 0.100 s 0.001 0.005 Debounce time for input 2
OscillationCount2 0 - 255 - 1 0 Oscillation count for input 2
OscillationTime2 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 2
Threshold3 6 - 900 %UB 1 65 Threshold in percentage of station battery
voltage for input 3
DebounceTime3 0.000 - 0.100 s 0.001 0.005 Debounce time for input 3
OscillationCount3 0 - 255 - 1 0 Oscillation count for input 3
OscillationTime3 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 3
Threshold4 6 - 900 %UB 1 65 Threshold in percentage of station battery
voltage for input 4
DebounceTime4 0.000 - 0.100 s 0.001 0.005 Debounce time for input 4
OscillationCount4 0 - 255 - 1 0 Oscillation count for input 4
OscillationTime4 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 4
Threshold5 6 - 900 %UB 1 65 Threshold in percentage of station battery
voltage for input 5
DebounceTime5 0.000 - 0.100 s 0.001 0.005 Debounce time for input 5
OscillationCount5 0 - 255 - 1 0 Oscillation count for input 5
OscillationTime5 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 5
Threshold6 6 - 900 %UB 1 65 Threshold in percentage of station battery
voltage for input 6
DebounceTime6 0.000 - 0.100 s 0.001 0.005 Debounce time for input 6
OscillationCount6 0 - 255 - 1 0 Oscillation count for input 6
Table continues on next page
Section 4 1MRK 504 135-UEN A
Binary input and output modules
52
Technical manual

Table of Contents

Other manuals for ABB ret650

Related product manuals