16.12.3 Function block
PRPSTATUS
LAN1-A
LAN1-B
IEC13000011-1-en.vsd
IEC13000011 V1 EN
Figure 247: PRPSTATUS function block
Table 468: PRPSTATUS Output signals
Name Type Description
LAN1-A BOOLEAN LAN1 channel A status
LAN1-B BOOLEAN LAN1 channel B status
16.12.4 Setting parameters
The PRPSTATUS function has no user settings.
However, the redundant communication is configured in the LHMI under Main
menu/Configuration/Communication/TCP-IP configuration/ETHLAN1_AB
where Operation mode, IPAddress and IPMask are configured.
16.13 Activity logging parameters ACTIVLOG
16.13.1 Activity logging ACTIVLOG
ACTIVLOG contains all settings for activity logging.
There can be 6 external log servers to send syslog events to. Each server can be
configured with IP address; IP port number and protocol format. The format can be
either syslog (RFC 5424) or Common Event Format (CEF) from ArcSight.
16.13.2 Settings
Table 469: ACTIVLOG Non group settings (basic)
Name
Values (Range) Unit Step Default Description
ExtLogSrv1Type Off
SYSLOG UDP/IP
SYSLOG TCP/IP
CEF TCP/IP
-
- Off External log server 1 type
ExtLogSrv1Port 1 - 65535 - 1 514 External log server 1 port number
ExtLogSrv1IP 0 - 18 IP
Address
1 127.0.0.1 External log server 1 IP-address