actually set and configured values within the IED. No settings will be changed, thus
mistakes are avoided.
Forcing of binary output signals is only possible when the IED is in test mode.
17.4.3 Function block
TESTMODE
INPUT ACTIVE
OUTPUT
SETTING
NOEVENT
IEC09000219-1.vsd
IEC09000219 V1 EN
Figure 256: TESTMODE function block
17.4.4 Signals
Table 487: TESTMODE Input signals
Name
Type Default Description
INPUT BOOLEAN 0 Sets terminal in test mode when active
Table 488: TESTMODE Output signals
Name
Type Description
ACTIVE BOOLEAN Terminal in test mode when active
OUTPUT BOOLEAN Test input is active
SETTING BOOLEAN Test mode setting is (On) or not (Off)
NOEVENT BOOLEAN Event disabled during testmode
17.4.5 Settings
Table 489: TESTMODE Non group settings (basic)
Name
Values (Range) Unit Step Default Description
TestMode Off
On
- - Off Test mode in operation (On) or not (Off)
EventDisable Off
On
- - Off Event disable during testmode
CmdTestBit Off
On
- - Off Command bit for test required or not
during testmode
1MRK 504 135-UEN A Section 17
Basic IED functions
575
Technical manual