ABB ret650 - Technical Data

ABB ret650
670 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
a
b
a>b
BLOCK
AND
I
OP
Extract second
harmonic current
component
Extract
fundamental
current component
X
2ndHarmStab
a
b
a>b
a
b
a>b
0.07*IBase
IEC13000015-1-en.vsd
2
N
D
H
A
R
M
D
UseStartValue
IN1>
IN2>
IN3>
IN4>
a
b
a>b
|I
OP
|
t
t=70ms
OR
AN
D
BlkParTransf=On
q
-1
OR
2ndH_BLOCK_Int
IEC13000015 V1 EN
Figure 75: Second harmonic blocking
8.4.9 Technical data
Table 90: EF4PTOC technical data
Function
Range or value Accuracy
Operate current (1-2500)% of
lBase
± 1.0% of I
r
at I < I
r
± 1.0% of I at I > I
r
Reset ratio > 95% -
Operate current for directional
comparison, Zero sequence
(1–100)% of
lBase
± 2.0% of I
r
Operate current for directional
comparison, Negative sequence
(1–100)% of
lBase
± 2.0% of I
r
Min. operating current (1-10000)% of
lBase
± 1.0% of I
r
at I < I
r
± 1.0% of I at I >I
r
Minimum operate time for inverse
characteristics
(0.000-60.000) s ± 0.5% ± 25 ms
Timers (0.000-60.000) s
± 0.5% ±25 ms
Inverse characteristics, see table
559, table 560 and table 561
15 curve types
1)
ANSI/IEEE C37.112
IEC 60255–151
±3% or ±40 ms
0.10 ≤ k ≤ 3.00
1.5 x I
set
≤ I ≤ 20 x I
set
Table continues on next page
1MRK 504 135-UEN A Section 8
Current protection
171
Technical manual