Table 467: RS485103 Non group settings (basic)
Name Values (Range) Unit Step Default Description
SlaveAddress 1 - 255 - 1 1 Slave address
BaudRate 9600 Bd
19200 Bd
- - 9600 Bd Baudrate on serial line
CycMeasRepTime 1.0 - 1800.0 s 0.1 5.0 Cyclic reporting time of measurments
MasterTimeDomain UTC
Local
Local with DST
-
- UTC Master time domain
TimeSyncMode IEDTime
LinMastTime
IEDTimeSkew
-
- IEDTime Time synchronization mode
EvalTimeAccuracy Off
5ms
10ms
20ms
40ms
-
- 5ms Evaluate time accuracy for invalid time
EventRepMode SeqOfEvent
HiPriSpont
- - SeqOfEvent Event reporting mode
16.12 IEC 61850-8-1 redundant station bus communication
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
System component for parallel
redundancy protocol
PRPSTATUS - -
16.12.1 Functionality
Redundant station bus communication according to IEC 62439-3 Edition 2 is
available as option in the Customized 650 Ver 1.3 series IEDs, and the selection is
made at ordering. Redundant station bus communication according to IEC 62439-3
Edition 2 uses both ports LAN1A and LAN1B on the COM03 module.
Select COM03 for redundant station bus according to IEC 62439-3
Edition 2 protocol, at the time of ordering.
IEC 62439-3 Edition 2 is NOT compatible with IEC 62439-3 Edition
1.
16.12.2 Principle of operation
The redundant station bus communication is configured using the local HMI, Main
Menu/Configuration/Communication/TCP-IP configuation/ETHLAN1_AB.
The settings are also visible in PST in PCM600.
1MRK 504 135-UEN A Section 16
Station communication
551
Technical manual