OVEREXCITATION IN %
Time (s)
IEEE OVEREXCITATION CURVES
IEC09000115-1-en.vsd
(M-Emaxcont)*100)
IEC09000115 V1 EN
Figure 100: Delays inversely proportional to the square of the overexcitation
The critical value of excitation M is determined via OEXPVPH setting V/Hz>>. V/
Hz>> can be thought of as a no-load voltage at rated frequency, where the inverse law
should be replaced by a short definite delay, tMin. If, for example, V/Hz>> = 140 %,
then M is according to equation
83.
( )
V Hz>> / f
M 1.40
Ur/fr
= =
IECEQUATION2286 V1 EN (Equation 83)
9.4.7.3 Cooling
The overexcitation protection function (OEXPVPH) is basically a thermal protection,
therefore a cooling process has been introduced. An exponential cooling process is
Section 9 1MRK 504 135-UEN A
Voltage protection
228
Technical manual

Table of Contents