EasyManua.ls Logo

ABB ret650 - Section 20 IED and Functionality Tests; Electromagnetic Compatibility Tests

ABB ret650
670 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 20 IED and functionality tests
20.1 Electromagnetic compatibility tests
Table 554: Electromagnetic compatibility tests
Description Type test value Reference
100 kHz and 1 MHz burst
disturbance test
IEC 61000-4-18, level 3
IEC 60255-22-1
ANSI C37.90.1-2012
Common mode
2.5 kV
Differential mode 2.5 kV
Electrostatic discharge test IEC 61000-4-2, level 4
IEC 60255-22-2
ANSI C37.90.3-2001
Contact discharge
8 kV
Air discharge 15 kV
Radio frequency interference
tests
Conducted, common
mode
10 V (emf), f=150 kHz...80 MHz IEC 61000-4-6 , level 3
IEC 60255-22-6
Radiated, amplitude-
modulated
20 V/m (rms), f=80...1000 MHz
and f=1.4...2.7 GHz
IEC 61000-4-3, level 3
IEC 60255-22-3
ANSI C37.90.2-2004
Fast transient disturbance tests
IEC 61000-4-4
IEC 60255-22-4, class A
ANSI C37.90.1-2012
Communication ports
4 kV
Other ports 4 kV
Surge immunity test IEC 61000-4-5
IEC 60255-22-5
Communication 1 kV line-to-earth
Other ports 2 kV line-to-earth, 1 kV line-to-
line
Power supply 4 kV line-to-earth, 2 kV line-to-
line
Power frequency (50 Hz)
magnetic field
IEC 61000-4-8, level 5
3 s 1000 A/m
Table continues on next page
1MRK 504 135-UEN A Section 20
IED and functionality tests
621
Technical manual

Table of Contents

Other manuals for ABB ret650