17.16.4 Operation principle
The Denial of service functions (DOSLAN1 and DOSFRNT) measures the IED load
from communication and, if necessary, limit it for not jeopardizing the IEDs control
and protection functionality due to high CPU load. The function has the following
outputs:
LINKUP indicates the Ethernet link status
WARNING indicates that communication (frame rate) is higher than normal
ALARM indicates that the IED limits communication
Section 17 1MRK 504 135-UEN A
Basic IED functions
600
Technical manual