principle. The master must have software that can interpret IEC 60870-5-103
communication messages.
Function blocks available for the IEC 60870–5–103 protocol are described in sections
Control and Monitoring.The Communication protocol manual for IEC 60870-5-103
includes the 650 series vendor specific IEC 60870-5-103 implementation.
IEC 60870-5-103 protocol can be configured to use either the optical serial or RS485
serial communication interface on the COM03 or the COM05 communication
module. The functions Operation selection for optical serial OPTICALPROT and
Operation selection for RS485 RS485PROT are used to select the communication
interface.
See the Engineering manual for IEC103 60870-5-103 engineering
procedures in PCM600.
The function IEC60870-5-103 Optical serial communication, OPTICAL103, is used
to configure the communication parameters for the optical serial communication
interface. The function IEC60870-5-103 serial communication for RS485,
RS485103, is used to configure the communication parameters for the RS485 serial
communication interface.
16.11.2 Settings
Table 466: OPTICAL103 Non group settings (basic)
Name
Values (Range) Unit Step Default Description
SlaveAddress 1 - 255 - 1 1 Slave address
BaudRate 9600 Bd
19200 Bd
- - 9600 Bd Baudrate on serial line
RevPolarity Off
On
- - On Invert polarity
CycMeasRepTime 1.0 - 1800.0 s 0.1 5.0 Cyclic reporting time of measurments
MasterTimeDomain UTC
Local
Local with DST
-
- UTC Master time domain
TimeSyncMode IEDTime
LinMastTime
IEDTimeSkew
-
- IEDTime Time synchronization mode
EvalTimeAccuracy Off
5ms
10ms
20ms
40ms
-
- 5ms Evaluate time accuracy for invalid time
EventRepMode SeqOfEvent
HiPriSpont
- - SeqOfEvent Event reporting mode