Via a mA input signal
12.3.4.3 Connection between TR8ATCC and TCMYLTC
The two function blocks Automatic voltage control for tap changer, TR8ATCC and
Tap changer control and supervision, 6 binary inputs TCMYLTC are connected to
each other according to figure
153 below.
(Rmk. In case
of parallel
control, this
signal shall
also be
connected to
HORIZx input
of the parallel
transformer
ATCC function
block)
IEC09000326_1_en.vsd
TR8ATCC
I3P1*
I3P2*
U3P2*
HORIZ1*
HORIZ2*
HORIZ3*
HORIZ4*
ATCCIN*
BLOCK
MANCTRL
AUTOCTRL
PSTO
RAISEV
LOWERV
EAUTOBLK
DEBLKAUT
LVA1
LVA2
LVA3
LVA4
LVARESET
RSTERR
DISC
SNGLMODE
T1INCLD
T2INCLD
T3INCLD
T4INCLD
FORCMAST
RSTMAST
ATCCOUT
MAN
AUTO
IBLK
PGTFWD
PLTREV
QGTFWD
QLTREV
UHIGH
ULOW
UBLK
HOURHUNT
DAYHUNT
HUNTING
SINGLE
PARALLEL
TIMERON
ADAPT
TOTBLK
AUTOBLK
MASTER
FOLLOWER
MFERR
OUTOFPOS
UGTUPPDB
ULTLOWDB
COMMERR
ICIRC
TRFDISC
VTALARM
T1PG
T2PG
T3PG
T4PG
TCMYLTC
YLTCIN*
TCINPROG
INERR
RESETERR
OUTERR
RS_CLCNT
RS_OPCNT
PARITY
BIERR
B1
B2
B3
B4
B5
B6
MA
YLTCOUT
URAISE
ULOWER
HIPOSAL
LOPOSAL
POSERRAL
CMDERRAL
TCERRAL
POSOUT
CONVERR
NEWPOS
HIDIFPOS
INVALPOS
TCPOS
IEC09000326 V1 EN
Figure 153: Connection between TR8ATCC and TCMYLTC
The TR8ATCC function blocks have an output signal ATCCOUT, which is
connected to input YLTCIN on TCMYLTC. The data set sent from ATCCOUT to
YLTCIN contains 5 binary signals, one “word” containing 10 binary signals and 1
analog signal. For TR8ATCC data is also sent from output ATCCOUT to other
TR8ATCC function input HORIZx, when the master-follower or circulating current
mode is used.
Table 237: Binary signals: ATCCOUT / YLTCIN
Signal
Description
raiseVolt Order to TCMYLTC to make a raise command
lowerVolt Order to TCMYLTC to make a lower command
automaticCtrl The regulation is in automatic control
extRaiseBlock Block raise commands
extLowerBlock Block lower commands
Section 12 1MRK 504 135-UEN A
Control
348
Technical manual