EasyManua.ls Logo

ABB ret650 - Function Block; Identification; Signals

ABB ret650
670 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12.3.2.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Automatic voltage control for tap
changer
TR8ATCC
U
IEC10000166 V1 EN
90
12.3.2.2 Function block
TR8ATCC
I3P1*
I3P2*
U3P2*
HORIZ1*
HORIZ2*
HORIZ3*
HORIZ4*
ATCCIN*
BLOCK
MANCTRL
AUTOCTRL
PSTO
RAISEV
LOWERV
EAUTOBLK
DEBLKAUT
LVA1
LVA2
LVA3
LVA4
LVARESET
RSTERR
DISC
SNGLMODE
T1INCLD
T2INCLD
T3INCLD
T4INCLD
FORCMAST
RSTMAST
ATCCOUT
MAN
AUTO
IBLK
PGTFWD
PLTREV
QGTFWD
QLTREV
UHIGH
ULOW
UBLK
HOURHUNT
DAYHUNT
HUNTING
SINGLE
PARALLEL
TIMERON
ADAPT
TOTBLK
AUTOBLK
MASTER
FOLLOWER
MFERR
OUTOFPOS
UGTUPPDB
ULTLOWDB
COMMERR
ICIRC
TRFDISC
VTALARM
T1PG
T2PG
T3PG
T4PG
IEC09000325_1_en.vsd
IEC09000325 V1 EN
Figure 150: TR8ATCC function block
12.3.2.3 Signals
Table 225: TR8ATCC Input signals
Name
Type Default Description
I3P1 GROUP
SIGNAL
- Input group for current on HV side
I3P2 GROUP
SIGNAL
- Input group for current on LV side
U3P2 GROUP
SIGNAL
- Input group for voltage on LV side
BLOCK BOOLEAN 0 Block of function
MANCTRL BOOLEAN 0 Binary "MAN" command
AUTOCTRL BOOLEAN 0 Binary "AUTO" command
PSTO INTEGER 0 Operator place selection
RAISEV BOOLEAN 0 Binary "UP" command
Table continues on next page
Section 12 1MRK 504 135-UEN A
Control
332
Technical manual

Table of Contents

Other manuals for ABB ret650