EasyManua.ls Logo

ABB ret650 - Technical Data; Instantaneous Residual Overcurrent Protection EFPIOC; Identification

ABB ret650
670 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8.2.9 Technical data
Table 78: OC4PTOC technical data
Function
Setting range Accuracy
Operate current (5-2500)% of
lBase
± 1.0% of I
r
at I ≤ I
r
± 1.0% of I at I > I
r
Reset ratio > 95% at (50–2500)% of
lBase
-
Min. operating current (5-10000)% of
lBase
± 1.0% of I
r
at I ≤ I
r
±1.0% of I at I > I
r
2nd harmonic blocking (5–100)% of fundamental
± 2.0% of I
r
Independent time delay (0.000-60.000) s
± 0.5% ±25 ms
Minimum operate time for
inverse characteristics
(0.000-60.000) s
± 0.5% ±25 ms
Inverse characteristics, see
table 559, table 560 and table
561
15 curve types
1)
ANSI/IEEE C37.112
IEC 60255–151
±3% or ±40 ms
0.10 ≤ k ≤ 3.00
1.5 x I
set
≤ I ≤ 20 x I
set
Operate time, nondirectional
start function
25 ms typically at 0 to 2 x I
set
-
Reset time, nondirectional start
function
35 ms typically at 2 to 0 x I
set
-
Operate time, directional start
function
50 ms typically at 0 to 2 x I
set
-
Reset time, directional start
function
35 ms typically at 2 to 0 x I
set
-
Critical impulse time 10 ms typically at 0 to 2 x I
set
-
Impulse margin time 15 ms typically -
1)
Note: Timing accuracy only valid when 2nd harmonic blocking is turned off
8.3 Instantaneous residual overcurrent protection
EFPIOC
8.3.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Instantaneous residual overcurrent
protection
EFPIOC
IN>>
IEF V1 EN
50N
Section 8 1MRK 504 135-UEN A
Current protection
152
Technical manual

Table of Contents

Other manuals for ABB ret650

Related product manuals