16.9.2  Functionality
GOOSEMVRCV is used to receive measured value using IEC61850 protocol via
GOOSE.
16.9.3  Function block
IEC10000251-1-en.vsd
GOOSEMVRCV
BLOCK ^MVOUT
DATAVALID
COMMVALID
TEST
IEC10000251 V1 EN
Figure 244: GOOSEMVRCV function block
16.9.4  Signals
Table 460: GOOSEMVRCV Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
Table 461: GOOSEMVRCV Output signals
Name
Type Description
MVOUT REAL Measurand value output
DATAVALID BOOLEAN Data valid for measurand value output
COMMVALID BOOLEAN Communication valid for measurand value output
TEST BOOLEAN Test output
16.9.5  Settings
Table 462: GOOSEMVRCV Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off/On
16.9.6  Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.