Table 305: Truth table for RSMEMORY function block
RESET SET OUT NOUT
0 0 Last
value
Inverted last
value
0 1 0 1
1 0 1 0
1 1 0 1
Function block
RSMEMORY
SET
RESET
OUT
NOUT
IEC09000294-1-en.vsd
IEC09000294 V1 EN
Figure 177: RSMEMORY function block
Signals
Table 306: RSMEMORY Input signals
Name
Type Default Description
SET BOOLEAN 0 Input signal to set
RESET BOOLEAN 0 Input signal to reset
Table 307: RSMEMORY Output signals
Name
Type Description
OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal
Settings
Table 308: RSMEMORY Group settings (basic)
Name
Values (Range) Unit Step Default Description
Memory Off
On
- - On Operating mode of the memory function
1MRK 504 135-UEN A Section 13
Logic
389
Technical manual