Name Values (Range) Unit Step Default Description
CTStarPoint3 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec3 0.1 - 10.0 A 0.1 1 Rated CT secondary current
CTprim3 1 - 99999 A 1 1000 Rated CT primary current
CTStarPoint4 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec4 0.1 - 10.0 A 0.1 1.0 Rated CT secondary current
CTprim4 1 - 99999 A 1 1000 Rated CT primary current
CTStarPoint5 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec5 0.1 - 10.0 A 0.1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 1000 Rated CT primary current
CTStarPoint6 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec6 0.1 - 10.0 A 0.1 1.0 Rated CT secondary current
CTprim6 1 - 99999 A 1 1000 Rated CT primary current
VTsec7 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim7 0.001 - 9999.999 kV 0.001 132.000 Rated VT primary voltage
VTsec8 0.001 - 999.999 V 0.001 110 Rated VT secondary voltage
VTprim8 0.001 - 9999.999 kV 0.001 132 Rated VT primary voltage
VTsec9 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim9 0.001 - 9999.999 kV 0.001 132.000 Rated VT primary voltage
VTsec10 0.001 - 999.999 V 0.001 110 Rated VT secondary voltage
VTprim10 0.001 - 9999.999 kV 0.001 132 Rated VT primary voltage
Table 7: AIM_4I_1I_5U Non group settings (basic)
Name
Values (Range) Unit Step Default Description
CTStarPoint1 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec1 0.1 - 10.0 A 0.1 1.0 Rated CT secondary current
CTprim1 1 - 99999 A 1 1000 Rated CT primary current
CTStarPoint2 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec2 0.1 - 10.0 A 0.1 1.0 Rated CT secondary current
CTprim2 1 - 99999 A 1 1000 Rated CT primary current
CTStarPoint3 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec3 0.1 - 10.0 A 0.1 1.0 Rated CT secondary current
CTprim3 1 - 99999 A 1 1000 Rated CT primary current
CTStarPoint4 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec4 0.1 - 10.0 A 0.1 1.0 Rated CT secondary current
Table continues on next page
1MRK 504 135-UEN A Section 3
Analog inputs
49
Technical manual