- 144 -UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Par.
No.
Menu
No.
Menu point name Display:
7-segm.
Default Range Description / remark take over
01 1.5
Show set
current 1
(4.3.4)
0.24-3200 A The UMC22 measures the currents
of the lines in the bushing holes. 3
wiring and/or the use of an external
current transformer result in a higher
power line current. To show e.g. the
real rated motor current the Current
factor can be changed, see menu
point Current factor in level Edit 2.
Depending on the Current factor the
number of stages before the decimal
point fi ts to the desired range.
-
1.5.1 show
0.24-63.00 A
0.42-109.0 A
50- 3200 A
- Displayed range at
Current factor = 1.0 (default)
- Displayed range at
Current factor = 1.7 (for 3 circuitry)
- Displayed range at
Current factor > 10
(for external current transformer,
secondary current 5 A)
03 1.6
Show set
current 2
(4.3.4)
Set current of winding 2 of 2-speed-
motors.
-
1.6.1 show
see show Set current 1
- 1.7
Version
Firmware-version of UMC22 -
18 1.8
Operating hours
(4.3.4)
All hours are counted but the unit
place is not displayed in the Control
Panel (10 hour steps). Displayed fi gu-
res 00.00-65.53 correspond with real
00'000-65'530.
-
1.8.1 show
0 0-65'535
19 1.9
Number of starts
(4.3.4)
All starts are counted but the three
lower places are not displayed on the
Control Panel. The displayed range
0000-1000 corresponds with real
0-1'000'000.
-
1.9.1 show
0 0-1'000'000